The Energy Efficiency Factor when deciding between VSD or Soft Starter.

This is where the comparison becomes most important for running costs.

A soft starter saves energy only during the brief starting period. Once the motor is running, it draws the same power it would on a DOL starter. If your application runs a pump or fan at full speed all day, a soft starter does nothing for your electricity bill during those running hours.

A VSD, by contrast, can deliver dramatic energy savings continuously. For centrifugal loads (pumps, fans, blowers), power consumption follows the cube law — meaning small reductions in speed produce large reductions in energy use. A fan running at 80% speed uses only about 51% of the energy it would at full speed. Over a year of continuous operation, this saving typically pays back the higher cost of a VSD within 12 to 24 months.

In South Africa’s current energy cost environment, this payback case is stronger than ever.

The Decision in Plain Terms

VFD/VSD Soft Starter
Controls starting
Controls speed during operation
Energy savings at startup Moderate Moderate
Upfront cost Higher Lower
Long-term running cost Lower Higher
Process / Speed control Yes No
Best for Variable-speed loads Fixed-speed loads